29 CFR 1926.350: Gas welding and cutting
The official text is on the eCFR. This page maps how the section is organized, quotes the paragraphs our ASP, CHST practice questions are built on, and gives free questions you can try. Text below is quoted from the eCFR, current as of 2026-10-14; the section was last amended 2016-09-01.
How 29 CFR 1926.350 is organized
- (a) Transporting, moving, and storing compressed gas cylinders12 paragraphs
- (b) Placing cylinders4 paragraphs
- (c) Treatment of cylinders3 paragraphs
- (d) Use of fuel gas7 paragraphs
- (e) Fuel gas and oxygen manifolds5 paragraphs
- (f) Hose7 paragraphs
- (g) Torches3 paragraphs
- (h) Regulators and gauges1 paragraph
- (i) Oil and grease hazards1 paragraph
- (j) Additional rules1 paragraph
Paragraphs our practice questions cite most
Counted across the 11 live PassCited questions built on this section. This reflects our question bank, not the real exam.
“(2) Torches in use shall be inspected at the beginning of each working shift for leaking shutoff valves, hose couplings, and tip connections. Defective torches shall not be used.”
“(6) Unless cylinders are firmly secured on a special carrier intended for this purpose, regulators shall be removed and valve protection caps put in place before cylinders are moved.”
“(11) Inside of buildings, cylinders shall be stored in a well-protected, well-ventilated, dry location, at least 20 feet (6.1 m) from highly combustible materials such as oil or excelsior. Cylinders should be stored in definitely assigned places away from elevators, stairs, or gangways. Assigned storage places shall be located where cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers and cupboards.”
“(c) Treatment of cylinders. (1) Cylinders, whether full or empty, shall not be used as rollers or supports.”
“(1) Before a regulator to a cylinder valve is connected, the valve shall be opened slightly and closed immediately. (This action is generally termed “cracking” and is intended to clear the valve of dust or dirt that might otherwise enter the regulator.) The person cracking the valve shall stand to one side of the outlet, not in front of it. The valve of a fuel gas cylinder shall not be cracked where the gas would reach welding work, sparks, flame, or other possible sources of ignition.”
Free practice questions on 29 CFR 1926.350
Question 1
A crew needs to move an oxygen cylinder to a different work area on a flatbed truck. The cylinder is not on a special carrier. Which action is required before the cylinder is moved?
Show answer and source
Answer: D. Remove the regulator and put the valve protection cap in place
The standard requires regulators to be removed and valve protection caps put in place before cylinders are moved, unless the cylinders are firmly secured on a special carrier made for that purpose. Leaving the regulator on exposes the valve and fittings to damage. Powered-vehicle transport also requires cylinders to be secured vertically, so laying the cylinder down is wrong.
Answer D rests on
29 CFR 1926.350(a)(6)(opens ecfr.gov in a new tab)“Unless cylinders are firmly secured on a special carrier intended for this purpose, regulators shall be removed and valve protection caps put in place before cylinders are moved.”
Question 2
A welder on a construction site starts the day shift with an oxy-fuel cutting torch that was used and put away without incident by the night shift. Before lighting it, she opens the gas supply and hears a faint hiss and sees bubbles forming in a soap-solution test at the hose coupling nut. A coworker says the torch was fine yesterday and she can just tighten it later if the leak gets worse. What does the standard require?
Show answer and source
Answer: C. Do not use the torch because the leaking coupling is a defect found at the start-of-shift inspection; it must be repaired or replaced first
The standard requires torches in use to be inspected at the start of each shift for leaking shutoff valves, hose couplings, and tip connections, and defective torches must not be used. Yesterday's good condition does not excuse the leak, and matches are not permitted lighting devices.
Answer C rests on
29 CFR 1926.350(g)(2)(opens ecfr.gov in a new tab)“Torches in use shall be inspected at the beginning of each working shift for leaking shutoff valves, hose couplings, and tip connections. Defective torches shall not be used.”
Question 3
A contractor runs oxy-fuel cutting on a two-shift schedule. The day crew inspected the oxygen and acetylene hoses at the start of their shift and found them in good condition. When the night crew arrives, the lead says the hoses were already checked that day, so they can start cutting right away. No incidents were reported during the day shift. What does the standard require?
Show answer and source
Answer: A. The night crew must inspect the hoses at the start of their own shift and remove any defective hose from service.
The standard requires hose in use to be inspected at the beginning of each working shift, so the day crew's inspection does not cover the night shift. Pressure testing is tied to a flashback or severe wear or damage, which is not the case here.
Answer A rests on
29 CFR 1926.350(f)(3)(opens ecfr.gov in a new tab)“All hose in use, carrying acetylene, oxygen, natural or manufactured fuel gas, or any gas or substance which may ignite or enter into combustion, or be in any way harmful to employees, shall be inspected at the beginning of each working shift. Defective hose shall be removed from service.”
Question 4
A crew will keep several compressed gas cylinders inside a building overnight. The supervisor compares four possible locations. Which location complies with the standard for indoor cylinder storage?
Show answer and source
Answer: B. A marked, assigned spot in a dry, well-ventilated room, away from stairs and traffic lanes, with nothing stored overhead that could fall
The standard calls for definitely assigned places away from elevators, stairs, or gangways, where cylinders will not be knocked over or hit by passing or falling objects. The closed locker is tempting because it prevents tampering, but the standard bars keeping cylinders in unventilated enclosures such as lockers and cupboards.
Answer B rests on
29 CFR 1926.350(a)(11)(opens ecfr.gov in a new tab)“Cylinders should be stored in definitely assigned places away from elevators, stairs, or gangways. Assigned storage places shall be located where cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers and cupboards.”
Question 5
A welder opens the valve on an acetylene cylinder and smells gas. Soapy water shows bubbles around the valve stem. She closes the valve and tightens the gland nut, but when she reopens the valve the stem still leaks. The cylinder is still about half full, and the crew wants to finish the shift's work. What action does the standard require?
Show answer and source
Answer: B. Discontinue use of the cylinder, tag it properly, and remove it from the work area
The leak is at the valve stem and did not stop after the gland nut was tightened. The standard then requires the cylinder to be taken out of use, tagged, and removed from the work area. The regulator exception applies only to a leak through the valve seat, not to a stem leak.
Answer B rests on
29 CFR 1926.350(d)(5)(opens ecfr.gov in a new tab)“If, when the valve on a fuel gas cylinder is opened, there is found to be a leak around the valve stem, the valve shall be closed and the gland nut tightened. If this action does not stop the leak, the use of the cylinder shall be discontinued, and it shall be properly tagged and removed from the work area.”