Compressed Gases questions for the ASP
ASP11 Domain 2: Safety Programs and Concepts (2.8.l Compressed gasses/pressure vessels). 3 free questions below. Every answer quotes and links the regulation paragraph it rests on.
Regulations covered
- 29 CFR 1910.101 Compressed gases (general requirements).
- 29 CFR 1926.350 Gas welding and cutting.How this section is tested
Text pulled from the eCFR, current as of 2026-10-14.
Question 1
A welder on a construction site starts the day shift with an oxy-fuel cutting torch that was used and put away without incident by the night shift. Before lighting it, she opens the gas supply and hears a faint hiss and sees bubbles forming in a soap-solution test at the hose coupling nut. A coworker says the torch was fine yesterday and she can just tighten it later if the leak gets worse. What does the standard require?
Show answer and source
Answer: C. Do not use the torch because the leaking coupling is a defect found at the start-of-shift inspection; it must be repaired or replaced first
The standard requires torches in use to be inspected at the start of each shift for leaking shutoff valves, hose couplings, and tip connections, and defective torches must not be used. Yesterday's good condition does not excuse the leak, and matches are not permitted lighting devices.
Answer C rests on
29 CFR 1926.350(g)(2)(opens ecfr.gov in a new tab)“Torches in use shall be inspected at the beginning of each working shift for leaking shutoff valves, hose couplings, and tip connections. Defective torches shall not be used.”
Question 2
A contractor runs oxy-fuel cutting on a two-shift schedule. The day crew inspected the oxygen and acetylene hoses at the start of their shift and found them in good condition. When the night crew arrives, the lead says the hoses were already checked that day, so they can start cutting right away. No incidents were reported during the day shift. What does the standard require?
Show answer and source
Answer: A. The night crew must inspect the hoses at the start of their own shift and remove any defective hose from service.
The standard requires hose in use to be inspected at the beginning of each working shift, so the day crew's inspection does not cover the night shift. Pressure testing is tied to a flashback or severe wear or damage, which is not the case here.
Answer A rests on
29 CFR 1926.350(f)(3)(opens ecfr.gov in a new tab)“All hose in use, carrying acetylene, oxygen, natural or manufactured fuel gas, or any gas or substance which may ignite or enter into combustion, or be in any way harmful to employees, shall be inspected at the beginning of each working shift. Defective hose shall be removed from service.”
Question 3
A crew will keep several compressed gas cylinders inside a building overnight. The supervisor compares four possible locations. Which location complies with the standard for indoor cylinder storage?
Show answer and source
Answer: B. A marked, assigned spot in a dry, well-ventilated room, away from stairs and traffic lanes, with nothing stored overhead that could fall
The standard calls for definitely assigned places away from elevators, stairs, or gangways, where cylinders will not be knocked over or hit by passing or falling objects. The closed locker is tempting because it prevents tampering, but the standard bars keeping cylinders in unventilated enclosures such as lockers and cupboards.
Answer B rests on
29 CFR 1926.350(a)(11)(opens ecfr.gov in a new tab)“Cylinders should be stored in definitely assigned places away from elevators, stairs, or gangways. Assigned storage places shall be located where cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers and cupboards.”
3 more compressed gases questions in the full ASP bank