Construction Fire Protection and Prevention practice questions for the CHST exam
CHST5 Domain 2: Emergency Preparedness, Incident Investigation, and Response (K2.1 Fire protection and prevention). 2 free questions below. Every answer quotes and links the regulation paragraph it rests on.
- 29 CFR 1926.150: Fire protection.
- 29 CFR 1926.151: Fire prevention.
- 29 CFR 1926.152: Flammable liquids. · how this section is tested
Text pulled from the eCFR, current as of 2026-10-14.
A site fuel truck is parked at a temporary fueling area to refill an excavator. The operator leaves the excavator idling to keep the cab heater running while the nozzle is in the tank. Which action does the standard require?
Show answer and source
Answer: D. Shut off the excavator's motor for the entire fueling operation
The standard requires the motors of all equipment being fueled to be shut off during fueling. A nearby extinguisher, fire watch, or bonding does not replace that requirement.
“The motors of all equipment being fueled shall be shut off during the fueling operation.”
During an inspection of a temporary diesel (Category 4 flammable liquid) storage tank on a job site, you note the following about the vent piping: it terminates outdoors above the fill pipe opening and above the normal snow level, its outlet has a return bend with a coarse screen, and it enters the tank through the top. A horizontal run of the vent pipe has sagged between two supports, creating a low spot. Which condition is a deficiency that must be corrected?
Show answer and source
Answer: D. The sag in the horizontal run, because the pipe must drain toward the tank without sags or traps where liquid can collect
The standard requires vent pipes to be laid so they drain toward the tank without sags or traps in which liquid can collect, so the low spot must be fixed. The return bend and screen are expressly allowed to keep foreign material out, and the top entry and outlet above the fill pipe opening are what the standard requires.
“Vent pipes shall be so laid as to drain toward the tank without sags or traps in which liquid can collect. They shall be located so that they will not be subjected to physical damage.”
Unlock every CHST question with timed practice, the AI tutor and full-length mocks. Or start with the free diagnostic.