Electrical Safety-Related Work Practices practice questions for the ASP exam

ASP11 Domain 4: Fire Prevention and Protection (4.3 Electrical hazards and controls). 2 free questions below. Every answer quotes and links the regulation paragraph it rests on.

Regulations covered

Text pulled from the eCFR, current as of 2026-10-14.

Question 1

A maintenance crew has opened and locked out the disconnect for a motor circuit and the nominal voltage is 480 volts. Before the crew begins work, the qualified person operates the start controls and confirms the motor will not restart. She then tests the motor terminals with a voltage tester and finds no voltage. A technician points out that the control circuit shares a conduit with another circuit that is still energized, and that other equipment feeds the same motor leads. What must the qualified person's test also do before the circuit can be treated as deenergized?

Show answer and source

Answer: B. Determine whether any energized condition exists from inadvertently induced voltage or unrelated voltage backfeed, even though the circuit parts were deenergized and presumed safe

The standard requires the test to also determine whether any energized condition exists from induced voltage or backfeed, even where parts have been deenergized and presumed safe, which is exactly the concern with shared conduit and other feeds. The lock itself does not substitute for the test, and the standard assigns verification to a qualified person rather than to the employee who applied the lock.

“The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe.”
Question 2

On a construction site, a portable diesel generator feeds a distribution panel through a transformer-based separately derived system. The system is grounded, and the electrician is deciding where to make the connections to the grounding electrode. A coworker proposes landing the equipment grounding conductor and the grounding electrode conductor on the grounded circuit conductor at a terminal on the load side of the system's overcurrent devices, since the loads are located there. Which response is correct under the standard?

Show answer and source

Answer: A. Not acceptable; the connections must be made to the grounded circuit conductor on the supply side of the system disconnecting means or overcurrent devices

For a grounded separately derived system, the equipment grounding conductor and the grounding electrode conductor must both connect to the grounded circuit conductor on the supply side of the system disconnecting means or overcurrent devices, so a load-side connection does not comply. A continuous ground path is also required, but it does not change where the connection point must be.

“Both the equipment grounding conductor and the grounding electrode conductor shall be connected to the grounded circuit conductor on the supply side of the service disconnecting means, or on the supply side of the system disconnecting means or overcurrent devices if the system is separately derived.”
11 more electrical safety-related work practices questions in the full bank

Unlock every ASP question with timed practice, the AI tutor and full-length mocks. Or start with the free diagnostic.

Original practice questions, not real exam items. PassCited is not affiliated with or endorsed by BCSP.