Exit Routes questions for the ASP
ASP11 Domain 5: Emergency Preparedness and Response (5.3 Evacuation routes, life safety). 3 free questions below. Every answer quotes and links the regulation paragraph it rests on.
Regulations covered
- 29 CFR 1910.36 Design and construction requirements for exit routes.How this section is tested
- 29 CFR 1910.37 Maintenance, safeguards, and operational features for exit routes.How this section is tested
Text pulled from the eCFR, current as of 2026-10-14.
Question 1
A contractor is altering an office wing that employees will keep using. The required exit routes will stay open and unobstructed throughout the work. However, the work requires shutting off the wing's existing fire sprinkler system for two weeks. The manager says employees can stay because the job is temporary and the exits remain usable. Which action does the standard require?
Show answer and source
Answer: A. Employees may keep occupying the wing only if alternate fire protection that provides an equivalent level of safety is furnished while the sprinklers are off.
During alterations, employees may not occupy the workplace unless the exit routes are available and existing fire protections are maintained, or until alternate fire protection with an equivalent level of safety is furnished. Open exits alone are not enough once the sprinklers are disabled, and notifying employees does not replace equivalent protection.
Answer A rests on
29 CFR 1910.37(d)(2)(opens ecfr.gov in a new tab)“(2) During repairs or alterations, employees must not occupy a workplace unless the exit routes required by this subpart are available and existing fire protections are maintained, or until alternate fire protection is furnished that provides an equivalent level of safety.”
Question 2
A company is renovating the east wing of its occupied office building. The contractor proposes to shut off the existing sprinkler zone and close the east stairwell for three weeks while employees continue working on that floor. No temporary fire protection is planned, and the other stairwell is open but not enough to serve the area. Which action is required under the exit route standard before employees may keep occupying that floor?
Show answer and source
Answer: C. The required exit routes must be available and existing fire protections maintained, or alternate fire protection providing an equivalent level of safety must be furnished, or employees must not occupy the floor.
The standard bars employees from occupying a workplace during repairs or alterations unless exit routes are available and existing fire protections are maintained, or equivalent alternate fire protection is provided. An operable alarm, signage, or a limited fire watch does not replace the closed exit route and disabled sprinklers.
Answer C rests on
29 CFR 1910.37(d)(2)(opens ecfr.gov in a new tab)“(2) During repairs or alterations, employees must not occupy a workplace unless the exit routes required by this subpart are available and existing fire protections are maintained, or until alternate fire protection is furnished that provides an equivalent level of safety.”
Question 3
A safety professional is auditing a warehouse exit access corridor that leads to a single exit. The corridor is 36 inches wide for most of its length. A wall-mounted electrical cabinet protrudes into it, leaving a clear width of 31 inches at that point. A second location, where a rolling parts rack is routinely parked, leaves 26 inches clear. Which finding is correct under the exit route width requirements?
Show answer and source
Answer: D. The cabinet location complies but the rack location does not, because the exit access must be at least 28 inches wide at all points.
The standard requires an exit access to be at least 28 inches wide at all points, and projecting objects cannot reduce the width below the minimum. The 31-inch cabinet point meets this, but the 26-inch rack point does not. The 36-inch width is not the benchmark, so measuring against it is wrong.
Answer D rests on
29 CFR 1910.36(g)(2)(opens ecfr.gov in a new tab)“(2) An exit access must be at least 28 inches (71.1 cm) wide at all points. Where there is only one exit access leading to an exit or exit discharge, the width of the exit and exit discharge must be at least equal to the width of the exit access.”
3 more exit routes questions in the full ASP bank
Related topics
Original practice questions, not real exam items. PassCited is not affiliated with or endorsed by BCSP.