29 CFR 1910.333: Selection and use of work practices

The official text is on the eCFR. This page maps how the section is organized, quotes the paragraphs our ASP, CSP practice questions are built on, and gives free questions you can try. Text below is quoted from the eCFR, current as of 2026-10-14; the section was last amended 2017-01-01.

How 29 CFR 1910.333 is organized

  • (a) General6 paragraphs
  • (b) Working on or near exposed deenergized parts—(1) Application31 paragraphs
  • (c) Working on or near exposed energized parts—(1) Application39 paragraphs

Paragraphs our practice questions cite most

Counted across the 15 live PassCited questions built on this section. This reflects our question bank, not the real exam.

“(B) The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.”
“(3) Overhead lines. If work is to be performed near overhead lines, the lines shall be deenergized and grounded, or other protective measures shall be provided before work is started. If the lines are to be deenergized, arrangements shall be made with the person or organization that operates or controls the electric circuits involved to deenergize and ground them. If protective measures, such as guarding, isolating, or insulating are provided, these precautions shall prevent employees from contacting such lines directly with any part of their body or indirectly through conductive materials, to…”
“(D) Stored non-electrical energy in devices that could reenergize electric circuit parts shall be blocked or relieved to the extent that the circuit parts could not be accidentally energized by the device.”
“(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediatel…”
“(2) Work on energized equipment. Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.”

Free practice questions on 29 CFR 1910.333

Question 1

A maintenance crew is about to service a motor control circuit on a conveyor. The electrician proposes to stop the conveyor with the push-button stop station and the safety interlock on the guard, then begin work without opening the main disconnect, because the controls show the circuit is 'off.' Under the standard, what is the correct response?

Show answer and source

Answer: B. Not acceptable; control circuit devices and interlocks may not be the sole means of deenergizing or substitute for lockout and tagging

The standard bars control circuit devices such as push buttons, selector switches and interlocks from being the sole means of deenergizing, and interlocks cannot replace lockout and tagging. Combining two of these devices still leaves no disconnection from the energy source.

Answer B rests on

29 CFR 1910.333(b)(2)(ii)(B)(opens ecfr.gov in a new tab)
“Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.”

Report a problem

We re-check reported questions against the regulation and fix or remove them.

Question 2

A contractor's crew will repaint a rooftop sign that sits close to an uninsulated utility distribution line owned and operated by the local power company. The employer decides not to install guarding or insulation and instead wants the line deenergized for the job. Which action satisfies the standard before the crew starts work?

Show answer and source

Answer: B. Make arrangements with the utility that operates or controls the line to deenergize and ground it before work starts

When the line is to be deenergized, the standard requires arrangements with the person or organization that operates or controls the circuits to deenergize and ground them, and this must be done before work begins. Opening the building's disconnect does not affect the utility's line. Waiting until a hazard develops, or judging by sight or sound, also does not meet the requirement.

Answer B rests on

29 CFR 1910.333(c)(3)(opens ecfr.gov in a new tab)
“If the lines are to be deenergized, arrangements shall be made with the person or organization that operates or controls the electric circuits involved to deenergize and ground them.”

Report a problem

We re-check reported questions against the regulation and fix or remove them.

Question 3

A maintenance crew has opened and locked out the disconnect for a motor circuit and the nominal voltage is 480 volts. Before the crew begins work, the qualified person operates the start controls and confirms the motor will not restart. She then tests the motor terminals with a voltage tester and finds no voltage. A technician points out that the control circuit shares a conduit with another circuit that is still energized, and that other equipment feeds the same motor leads. What must the qualified person's test also do before the circuit can be treated as deenergized?

Show answer and source

Answer: B. Determine whether any energized condition exists from inadvertently induced voltage or unrelated voltage backfeed, even though the circuit parts were deenergized and presumed safe

The standard requires the test to also determine whether any energized condition exists from induced voltage or backfeed, even where parts have been deenergized and presumed safe, which is exactly the concern with shared conduit and other feeds. The lock itself does not substitute for the test, and the standard assigns verification to a qualified person rather than to the employee who applied the lock.

Answer B rests on

29 CFR 1910.333(b)(2)(iv)(B)(opens ecfr.gov in a new tab)
“The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe.”

Report a problem

We re-check reported questions against the regulation and fix or remove them.

Question 4

A maintenance technician must replace a lamp holder in a switchgear room. Exposed energized bus bars run along the wall next to the work spot. The only ladder on hand is an aluminum stepladder, and the technician could easily lean the ladder against, or sway into, the bus bars while working. What must the employer do before the task goes ahead?

Show answer and source

Answer: A. Provide a portable ladder with nonconductive siderails, because the ladder or the employee could contact exposed energized parts

The ladder or the employee could contact exposed energized bus bars, so the standard requires a ladder with nonconductive siderails. Having a coworker hold the base or removing jewelry does not change the ladder's conductivity, and the standard sets no exception for those measures.

Answer A rests on

29 CFR 1910.333(c)(7)(opens ecfr.gov in a new tab)
“Portable ladders shall have nonconductive siderails if they are used where the employee or the ladder could contact exposed energized parts.”

Report a problem

We re-check reported questions against the regulation and fix or remove them.