Excavations and Trenching practice questions for the CHST exam
CHST5 Domain 1: Hazard and Risk Identification and Control (K1.3 Excavations). 3 free questions below. Every answer quotes and links the regulation paragraph it rests on.
- 29 CFR 1926.651: Specific excavation requirements. · how this section is tested
- 29 CFR 1926.652: Requirements for protective systems. · how this section is tested
Text pulled from the eCFR, current as of 2026-10-14.
A crew is excavating a 6-foot-deep utility trench on a site that was previously a landfill. The competent person asks when the atmosphere in the trench must be tested. According to the standard, when is testing required?
Show answer and source
Answer: A. Before employees enter the excavation, because a hazardous atmosphere could reasonably be expected and the depth is greater than 4 feet
The standard requires testing before employees enter excavations deeper than 4 feet where a hazardous atmosphere could reasonably be expected, such as in landfill areas. Waiting for symptoms or using a 12-foot threshold would not protect workers, and neither appears in the standard.
“Where oxygen deficiency (atmospheres containing less than 19.5 percent oxygen) or a hazardous atmosphere exists or could reasonably be expected to exist, such as in excavations in landfill areas or excavations in areas where hazardous substances are stored nearby, the atmospheres in the excavation shall be tested before employees enter excavations greater than 4 feet (1.22 m) in depth.”
A crew is installing a trench shield chosen from the manufacturer's tabulated data. On day two, the foreman finds that the trench will be deeper than the maximum depth in the manufacturer's data for that shield. The competent person has inspected the excavation and believes the shield can handle the extra depth. A supervisor suggests getting a verbal okay from the manufacturer's technical line and putting it in the daily log. Which action complies with the standard?
Show answer and source
Answer: C. Do not exceed the listed depth limit unless the manufacturer issues specific written approval, and keep that approval at the jobsite during construction of the protective system
A shield selected from manufacturer's tabulated data must be used within the manufacturer's limitations, and a deviation is allowed only with the manufacturer's specific written approval, which must be kept on the jobsite. A competent person's judgment or a verbal okay cannot replace that written approval.
“Deviation from the specifications, recommendations, and limitations issued or made by the manufacturer shall only be allowed after the manufacturer issues specific written approval.”
After a heavy overnight rainstorm, a competent person inspects a trench before the crew starts work. She finds water pooled along one wall and fresh soil sloughing from it. Two workers already in the trench are laying pipe, and the crew lead says the morning inspection is done, so work should continue and be rechecked at the end of the shift. What does the standard require?
Show answer and source
Answer: D. Remove the exposed employees from the trench until the necessary precautions have been taken to ensure their safety.
When the competent person finds evidence of a possible cave-in or other hazardous condition, the standard requires exposed employees to be removed from the hazardous area until precautions are in place. Waiting for the end of the shift is wrong because the daily inspection does not excuse leaving workers exposed. Spoil setback addresses material falling into the excavation, not an unstable wall.
“Where the competent person finds evidence of a situation that could result in a possible cave-in, indications of failure of protective systems, hazardous atmospheres, or other hazardous conditions, exposed employees shall be removed from the hazardous area until the necessary precautions have been taken to ensure their safety.”
Unlock every CHST question with timed practice, the AI tutor and full-length mocks. Or start with the free diagnostic.